EasyManua.ls Logo

System Sensor PDRP-2001 - C.1: NFPA 72 Auxiliary Fire Alarm System

System Sensor PDRP-2001
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114 PDRP-2001 Series Manual — P/N 53043:E4 7/28/2016
NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the PDRP-2001 main circuit board to supervise placement of 4XTMF module and
circuit.
3. Cut JP24 on the PDRP-2001 main circuit board to enable FACP Supervisory relay.
4. Refer to “4XTMF Municipal Box Transmitter Option Module” on page 31 for detailed
information.
FIRE
Gamewell Model M34-56 Local
Energy Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
Municipal Box Circuit
+
-
-
4XTMF
Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module

Table of Contents

Related product manuals