22 PDRP-2001 Series Manual — P/N 53043:E4 7/28/2016
Installation Operating Power
2.2 Operating Power
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the
panel is 120 VAC, 60 Hz, 3.66 amps for the PDRP-2001 or 240 VAC, 50 HZ, 2.085 amps for the
PDRP-2001E. Run a pair of wires (with ground conductor) from the protected premises main
breaker box to the AC terminal block TB1 on the main power supply. As per the National
Electrical Code, use 14 AWG (2.00 mm
2
, 1.6 mm O.D.) or heavier gauge wire with 600V
insulation. No other equipment may be connected to this circuit. In addition, this circuit must be
!
CAUTION: DISCONNECT ALL POWER BEFORE SERVICING
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL.
DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND
ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS,
MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
Figure 2.3 Backbox
9050udcab.cdr

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the System Sensor PDRP-2001 and is the answer not in the manual?

System Sensor PDRP-2001 Specifications

General IconGeneral
BrandSystem Sensor
ModelPDRP-2001
CategoryControl Panel
LanguageEnglish

Related product manuals