PDRP-2001 Series Manual — P/N 53043:E4 7/28/2016 13
Specifications Product Description
• Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silenced
Discharge
• Piezo sounder for alarm, trouble and supervisory
• 24 volt operation
• Low AC voltage sense
• Outputs Programmable for:
Releasing Solenoids
NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Nonsilenceable
– Release Stage Sounder
• Designed for sprinkler standards NFPA 13, 15 and 16
• Disable/Enable control per input zone and output zone
• Extensive transient protection
• Dual hazard operation
• Adjustable waterflow discharge timer and two soak timers
• Cross-zone (double-interlock) capability
• Pre-programmed and custom application templates
• Automatic battery charger with charger supervision
• Silent or audible walktest capabilities
• Optional Dress Panel DP-51050 (red)
• A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED
Annunciator module
• Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
• Optional CAC-5X Class A Converter Module for Outputs and IDCs
• Optional 4XTMF Municipal Box Transmitter Module
• Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
• Optional ANN-SEC card for secondary ANN-BUS
1.2 Specifications
AC Power
PDRP-2001/C: 120 VAC, 60 Hz, 3.66 amps
PDRP-2001E: 240 VAC, 50 Hz, 2.085 amps
Wire size: minimum #14 AWG (2.0 mm
2
) with 600V insulation
Supervised, nonpower-limited