English
When several SysAqua units are installed, ensure proper clearance is implemented around the
condensers specic to each machine.
Caution
12 SysAqua
9.2. CLEARANCE
When choosing the location for the
SysAqua, take care to leave sufcient
free clearance on all sides to ensure
easy access for maintenance work. The
minimum free clearance dimensions
indicated must be observed to ensure
both proper system operation and allow
access for maintenance and cleaning.
9.3. ATTACHMENT TO THE GROUND
The surface of the oor or structure located under the SysAqua must be at, and with sufcient strength
to withstand the unit's weight with its full liquid load, and occasional presence of maintenance equipment.
For normal applications, rigidity of the SysAqua and the positions of supports allow for an installation
minimizing vibrations. However, the installers can use anti-vibration rubber pads (supplied in option).
The SysAqua does not require anchoring on the foundations, except in regions exposed to a high earthquake
risk or if the device is installed on a high level on a steel frame.
When tting anti-vibration pads, refer to the manual supplied with the kit.
SysAqua 45/55/65/75/90/105/125
SysAqua 45/55/65/75/90/105/125
WITH BUFFER TANK