The manufacturer waives any liability for damage of a plate exchanger caused by water freezing
of water contained inside does not engage the responsibility of the manufacturer with respect to
this incident (low winter temperature or water start temperature below 5°C in summer mode).
Caution
44 SysAqua
In winter, after a general stoppage of the installation or a regulation malfunction, the water contained in the
hydraulic circuit may start freezing.
To prevent any problems if the hydraulic circuit is not glycolated, it is recommended to fully drain any circuits
not used and to pressurize them with nitrogen or protect them by adding an anti-freeze solution or other
measures.
The concentration of anti-freeze solution must be regularly and carefully checked before each winter
season.
17.3.3. WINTER PROTECTION
CAUTION
BEFORE CARRYING OUT ANY OPERATION ON THE EQUIPMENT, CHECK
THAT THE ELECTRICAL POWER SUPPLY IS SWITCHED OFF AND THAT IT
CANNOT BE SWITCHED ON INADVERTENTLY.
IT IS RECOMMENDED THAT THE DISCONNECT SWITCH BE PADLOCKED

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir SysAqua Series and is the answer not in the manual?

SystemAir SysAqua Series Specifications

General IconGeneral
BrandSystemAir
ModelSysAqua Series
CategoryChiller
LanguageEnglish

Related product manuals