Chapter 3 - Parameter List
31
Code Description
Keypad
Display
Setting Range Units
Factory
Default
Adj.
During
Run
Page
I/O-35 Acceleration Time 6 I 35 0.0 to 999.9 [sec] 0.1 30.0 [sec] Yes
I/O-36 Deceleration Time 6 I 36 0.0 to 999.9 [sec] 0.1 30.0 [sec] Yes
I/O-37 Acceleration Time 7 I 37 0.0 to 999.9 [sec] 0.1 20.0 [sec] Yes
I/O-38 Deceleration Time 7 I 38 0.0 to 999.9 [sec] 0.1 20.0 [sec] Yes
0 (Frequency)
1 (Current)
2 (Voltage)
I/O-40
FM (Frequency Meter) Output
Selection
I 40
3 (DC Link Vtg)
-
0
(Frequency)
Yes
I/O-41 FM Output Adjustment I 41 10 to 200 [%] 1 100 [%] Yes
67
I/O-42 Frequency Detection Level I 42 0 to FU1-20 0.01 30.00 [Hz] Yes
I/O-43 Frequency Detection Bandwidth I 43 0 to FU1-20 0.01 10.00 [Hz] Yes
68
0 (FDT-1)
1 (FDT-2)
2 (FDT-3)
3 (FDT-4)
4 (FDT-5)
5 (OL)
6 (IOL)
7 (Stall)
8 (OV)
9 (LV)
10 (OH)
11 (Lost Command)
12 (Run)
13 (Stop)
14 (Steady)
17 (Search)
I/O-44
Multi-function Output Define (MO)
15, 16, 18, 19
(-Reserved-)
I 44
20 (Ready)
- 12 (Run) Yes 68
I/O-45
Fault Output Relay Setting
(30A, 30B, 30C)
I 45
000 – 111 (bit set)
Bit 0: LV
Bit 1: All Trip
Bit 2: Auto Retry
- 010 Yes 71
I/O-46 Inverter Number I 46 1 to 250 1 1 Yes
0 (1200 bps)
1 (2400 bps)
2 (4800 bps)
3 (9600 bps)
I/O-47 Baud Rate I 47
4 (19200 bps)
- 3 (9600 bps) Yes
71
0 (None) I/O-48 Operating selection at Loss of Freq.
Reference
I 48
1 (Free Run)
- 0 (None) Yes 72

Related product manuals