83
-
507
-
013 Rev. D
9
CHAPTER 2 SPECIFICATIONS
2.1 OUTPUT RATING
MODEL
GEN
6-100
8-90
12.5-60
20-38
30-25
40-19
60-12.5
80-9.5
100-7.5
150-5
300-2.5
600-1.3
1.Rated output voltage (*1)
V
6
8
12.5
20
30
40
60
80
100
150
300
600
2.Rated output current 750W (*2)
A
100
90
60
38
25
19
12.5
9.5
7.5
5
2.5
1.3
3.Rated output power 750W
W
600
720
750
760
750
760
750
760
750
750
750
780
MODEL
GEN
6-200
8-180
12.5-120
20-76
30-50
40-38
50-30
60-25
80-19
100-15
150-10
300-5
600-2.6
1.Rated output voltage (*1)
V
6
8
12.5
20
30
40
50
60
80
100
150
300
600
2.Rated Output Current 1500W (*2)
A
200
180
120
76
50
38
30
25
19
15
10
5
2.6
3.Rated output power 1500W
W
1200
1440
1500
1520
1500
1520
1500
1500
1520
1500
1500
1500
1560
2.2 INPUT CHARACTERISTICS
V
6
8
12.5
20
30
40
50
60
80
100
150
300
600
1. Input voltage/freq. (*3)
2. Input current (at 100/200Vac)
A
3. Power Factor
4. 750W models Efficiency (*4)
%
76/78
77/80
81/84
82/85
82/85
83/87
83/87
83/87
83/87
83/87
83/87
83/87
83/87
5. 1500W modelsEfficiency (*4)
%
77/79
78/81
82/85
83/86
83/86
84/88
84/88
84/88
84/88
84/88
84/88
84/88
84/88
6. Inrush current at 100/200V
A
2.3 CONSTANT VOLTAGE MODE
V
6
8
12.5
20
30
40
50
60
80
100
150
300
600
1. Max.Line regulation (*5)
2. Max.Load regulation (*6)
3. Ripple and noise (p-p,20MHz) (*10)
mV
60
60
60
60
60
60
60
60
80
80
100
150
300
4. Ripple r.m.s., 5Hz~1MHz (*10)
mV
8
8
8
8
8
8
8
8
8
8
10
25
60
5. Temperature coefficient
PPM/°C
100PPM/°C of rated output voltage, following 30 minuteswarmup
6. Temperature drift
7. Rem. Sense compensation/wire
V
1
1
1
1
1.5
2
2
3
4
5
5
5
5
8. Up-prog. Response time 0~Vomax(*9)
mS
250
9. Down-prog. Response time: Full load
mS
10
250
No load
500
600
700
800
900
1000
1100
1100
1200
1500
2000
2500
4000
10. Transient response time
mS
11. Hold-up time
mS
2.4 CONSTANT CURRENTMODE
V
6
8
12.5
20
30
40
50
60
80
100
150
300
600
1. Max.line regulation (*5)
2. Max.load regulation (*7)
3. Ripple r.m.s. 5Hz~1MHz.750W (*8)
mA
200
180
120
76
63
48
38
29
23
18
13
8
1500W(*8)
mA
400
360
240
152
125
95
75
75
57
45
35
25
12
4. Temperature coefficient
PPM/°C
5. Temperature drift
2.5 ANALOGPROGRAMMING AND MONITORING
1.Voutvoltageprogramming
2. Iout voltage programming
3. Vout resistor progrmming
4. Iout resistor programming
5. On/off control
6. Output current monitor
7. Output voltage monitor
8. Power supplyOK signal
9. Parallel operation
10. Series operation
11. CV/CC inicator
12. Enable/Disable
13. Local/Remote analog control
14. Local/remote analog indicator
Dry contact. Open: off, Short: on. Max. voltage at Enable/Disable in: 6V.
By electrical signal or Open/Short: 0~0.6Vor short: Remote, 4~5Vor open: Local.
Open collector. Local:Open, Remote: On. Maximum voltage: 30V, maximum sink current: 5mA.
4~5V-OK, 0V-Fail, 500ohm seriesresistance.
Possible,up to 4 units in master/slave mode with single wire current balance connection.
Possible (with external diodes), up to 2units.
CV: TTL high (4~5V),source current: 10mA, CC: TTL low(0-0.6V).Sink current: 10mA .
Time for the output voltage to recoverwithin 0.5%of itsrated outputfor a load change 10~90% of rated
By electrical Voltage: 0~0.6V/2~15Vor drycontact, user selectable logic.
0~5V or 0~10V, user selectable.Accuracy: 1%
0~5V or 0~10V, user selectable.Accuracy: 1%
100PPM/°C from rated output current, following 30 minutes warm-up.
0.05% of ratedlout over 8hrs interval following 30 minutes warm-up. Constant line, load & temp.
output current.
Outputset-point: 10~100%.
Less than 1mSfor modelsup to and including 100V; 2mS for models above 100V.
85~265Vac continuous, 47-63Hz, single phase.
10.5/5 for 750W model, 21/11 for 1500W models.
0.99@100/200Vac, rated output power.
Less than 25A for 750W models, 50A for 1500W models.
0.01% of ratedoutput voltage +2mV
0.01% of ratedoutput voltage +2mV
0.05% of ratedVout over8hrs interval following 30 minuteswarm-up. Constant line, load & temp.
50
80
150
80
150
More than 20mS, 100Vac, rated output power.
0.01% of ratedoutput voltage +2mA
0.02% of ratedoutput current +5mA
0~100%, 0~5Vor 0~10V,user select. Accuracyand linearity; +/-0.5% of rated Vout.
0~100%, 0~5Vor 0~10V,user select. Accuracyand linearity; +/-1%of rated Iout.
0~100%, 0~5/10Kohm full scale, user select. Accuracyand linearity:+/-1%of rated Vout.
0~100%, 0~5/10Kohm full scale, user select. Accuracyand linearity:+/-1.5%of rated Iout.