HIGH
PRESSURE
LOC
K
A
IR
COOLED
COND.
WATER
COOLED
COND
AIR FLOW TO
CONDENSER TOO
LOW
AIR INLET
TEMPERATURE
TOO HIGH
FAN FAILS TO
OPERATE
REFRIGERATION
CIRCUIT OVER-
CHARGED
CHECK THERMAL
PROTECTIONS
AND POWER DRAWS
ELIMINATE
POSSIBLE
RECIRCULATION
OF EXPELLED AIR
MEASURE AIR
TEMPERATURE
CHECK COIL FOR
POSSIBLE
OBSTRUCTIONS
CHECK EFFICIENCY
OF CONDENSATION
CONTROL SYSTEM
CHECK AND
RETURN WITHIN
LIMITS
CLEAN
CONDENSER
COIL
REFRIGERATION
CIRCUIT OVER-
CHARGED
PRESSURE
CONTROLLED
VALVE FAULTY
LACK OF WATER
CONDENSER
DIRTY
WATER INLET
TEMPERATURE
VERY HIGH
CHECK PUMPS AND
SHUT-OFF VALVES
IN WATER CIRCUIT
CHECK
FUNCTIONALITY’?
ANDCALIBRATION
CHECK AND
RETURN WITHIN
LIMITS
CLEAN CHECK AND
RESTORE
ORIGINAL
CONDITIONS