12.3 HEATING SECTION PROBLEMS
NO
HEATING
HIGH
TEMPERATURE
WITH REDUCED
AIR FLOW
THERMAL
MAGNETIC
PROTECTION
TRIPPED
SHORT CIRCUIT IN
HEATER
OR TO EARTH
SAFETY
THERMOSTAT
TRIPPED
DISCONNECT
AND REPLACE
CLEAN THE AIR
FILTERS
CHECK AND
RESTORE DESIGN
CONDITIONS
CHECK
CONNECTIONS AND
FUNCTIONALITY OF
FANS
WATER
TEMPERATURE
TOO LOW
VALVE FAILED
TO OPEN
CHECK
FUNCTIONALITY OF
SERVO MOTOR
CHECK POWER
SUPPLY AND
MODULATING
SIGNAL
CHECK FOR
MECHANICAL
PROBLEMS IN VALVE
OPENING SYSTEM
CHECK AND
RESTORE
ELECTRICAL
DESIGN
CONDITIONS
TO WATER
NO HOT GAS
POST-
HEATING
NO
POST-HEATING
NO SERVO
CONTROL
FUNCTIONS
CHECK POWER
SUPPLY AND
MODULATING
SIGNAL
CHECK
FUNCTIONALITY
OF
SERVO CONTROL