12.1 DIRECT EXPANSION AIR CONDITIONERS - REFRIGERATION CIRCUIT PROBLEMS
LOW PRESSURE
LOCK
LACK OF
COMPRESSION
LOW AIR FLOW
THROUGH
EVAPORATOR
THERMOSTAT
VALVE FAULTY
REFRIGERATION
CIRCUIT NOT
CHARGED
LOW
CONDENSATIO
N PRESSURE
CHECK FAN
SETTINGS
CLEAN THE
AIR FILTERS
REPLACE
THE
BELLOWS
TRACE THE
LEAK AND
REPAIR
CHECK AIR
CIRCUIT AND
RESTORE
ORIGINAL
CONDITIONS
CHECK
CONDENSATION
CONTROL SYSTEM
MECHANICAL
FAILURE
VALVES
BROKEN
DISCONNECT
COMPRESSOR
AND REPLACE