15
V. OPERATING INSTRUCTION
CAUTION
If possible, before connecting the meter to the electrical equipment to be
tested, take off the electrical equipments power.
DANGER
Voltage input connectors U1 to U3 are common for input connector N, each
input connectors are not insulated.
Do not connect the unnecessary number of cords.
WARNING
Always set up the measurement first, then connect the test leads to the circuit.
Make connections to the instrument first, before connecting leads to a live
circuit.
Connect the ground lead first, then the voltage leads and the current probe,
Disconnect in reverse order.
Remove all test leads that are not in use.
U1 must be connected to voltage source during the measurement of U2, U3,
I1, I2 and I3, because U1 is the main signal source of the whole meter
measuring system. Otherwise you could not have any measurement from
U2, U3, I1, I2 and I3.
5-1 AC Current Adaptor
Safety Information
Read First: Safety Information
To ensure safe operation and service of the current clamp, follow these instructions:
Read the operating instructions before use and follow all safety instructions.
Use the Current Clamp only as specified in the operating instructions,
otherwise the clamp’s safety features may not protect you.
Adhere to local and national safety codes. Individual protective equipment
must be used to prevent shock and arc blast injury where hazardous live
conductors are exposed.
Do not hold the Current Clamp anywhere beyond the tactile barrier, see Figure 1.