29
5-6 Only One Current I4 Measurement
Application : Measurement any wire current independent of voltage, the
same as clamp meter application.
I3
I1
I4
I2
N
U1 U2
¢»
U3
1. Press
key to turn on the meter.
2. Press “I4” key.
3. Connect the I4 current probe output plug to the “I4” jack.
4. Press I4 current probe trigger to open the jaw and fully enclose desired measured
wire.
5. Read the I4 value, if the measured current value greater than 250A, the display will
show theOLsymbol.
5-7 Manual Data Memory and Read Function Operation
1. Clear memory data :
Press
key to turn off the meter.
Press and hold down the MEMORY key then press
key again to turn on the
meter, the “CLr” annunciator is displayed and all manual memories data is
cleared.