TS 910 TRANSFER SWITCH
PM140 REV 0 12/02/09 27 Thomson Technology
18.2. ELECTROSTATIC DISCHARGE PRECAUTIONS
CAUTION
contents subject to damage by
STATIC ELECTRICITY
The TSC 9 controller contains static-sensitive parts. Please observe the following anti-
static precautions at all times when handling this equipment. Failure to observe these
precautions may cause equipment failure and/or damage.
Discharge body static charge before handling the equipment (contact a grounded
surface and maintain contact while handling the equipment, a grounded wrist strap
can/should also be utilized).
Do not touch any components on the printed circuit board with your hands or any
other conductive equipment.
Do not place the equipment on or near materials such as Styrofoam, plastic and
vinyl. Place the equipment on grounded surfaces and only use an anti-static bag for
transporting the equipment.
18.3. DIELECTRIC TESTING
Do not perform any high voltage dielectric testing on the TSC 9 controller. The control
circuit isolation plug connected to the TSC 9 must be removed if high voltage dielectric
testing is performed on the transfer switch.