TSC 80e TRANSFER SWITCH CONTROLLER
PM091 Rev 1 09/02/27 Thomson Technology
49
function and a transfer is initiated to/from the
Generator & Utility supplies.
LIMIT SW FAILURE Contacts change state when one or both of the
ATS mechanism’s limit switch fails to signal the
controller following a transfer to a required
source.
REMOTE START Contacts change state when an engine start is
signaled during a test or Utility Power Failure.
Note: REMOTE STSRT function is only
programmable to Output #3.
4.6.10.1.Programmable Output #1
Programmable output #1 corresponds to the following output relay contacts:
Common- TB2 –29
Normally Closed- TB2 –30
Normally Open- TB2 –31
Note: Factory default setting for programmable output #1 is ATS Not in Auto
4.6.10.2.Programmable Output #2
Programmable output #2 corresponds to the following output relay contacts:
Common- TB2 –35
Normally Closed- TB2 –36
Normally Open- TB2 –37
Note: Factory default setting for programmable output #2 is Load Disconnect
Contact (LDC).
4.6.10.3.Programmable Output #3
Programmable output #3 corresponds to the following output relay contacts:
Common- TB2 –32
Normally Closed- TB2 –33
Normally Open- TB2 –34
Note: Factory default setting for programmable output #3 is Fail to Transfer.
4.6.10.4.Programmable Output #4
Programmable output #4 corresponds to the following output relay contacts:
Common- TB2 –14