What to do if my THOMSON TSC 7320 Controller will not transfer to generator source upon failure of utility source?
- AAnthony WattsAug 3, 2025
If the Thomson Controller doesn't transfer to the generator upon utility failure, several factors could be at play. * First, check if the warm-up time delay function has timed out by verifying the TSC 7320 timer setting. * Ensure the generator set output circuit breaker is closed. * Confirm the generator's voltage and frequency levels are correct and match the TSC 7320 settings. * Also, verify the phase rotation and check all TSC 7320 connectors, especially the generator voltage sensing connection plug. If the issue persists, there may be a ‘Transfer Fail’ alarm activated, a defective ATS mechanism motor, a loose control wire connection, or a defective TSC 7320 controller.