TSC 7320 Transfer Switch Controller
PM180 REV 0 23/02/10 Thomson Power Systems
22
3.6.7. CURRENT METERING PAGE
The current metering page is a subpage within the generator section, and it displays the
measured current as report from the CT’s for each of the lines.
NOTE: Load CT ‘s must be supplied with the ATS to provide current and power data.
3.6.8. SYNCHROSCOPE PAGE
The Synchroscope page is a subpage in the generator section and displays the voltage
difference and slip frequency difference between two available sources. This page will
also popup when changing sources on an ATS that is equipped with closed transition or
fast open transition in-sync transfer capability. This page will display the phase angle
difference, voltage difference and slip frequency difference between two available
sources.
3.6.9. ABOUT PAGE
The about page can be used to identify the firmware version of the controller, and the
software version.