TSC 7320 Transfer Switch Controller
PM180 REV 0 23/02/10 Thomson Power Systems
11
3.2. CONTROLLER INPUT CONNECTIONS
The TSC 7320 is provided from the factory with 14 programmable inputs with default settings
per table shown below. 8 of the inputs are digital inputs, and the other 6 are analogue inputs
that can also be programmed to be more digital inputs. Refer to the TSC 7320 Manual for further
information on programming changes as required.
NOTE: All control wiring required for any remote input connection must be made directly to the
door mounted TSC 7320 as per drawing below. All input wire cabling that may be installed must
be suitably routed and protected across the door hinge to prevent possible mechanical damage
upon door opening and/or door closing. Switch Control Unit internal PCB is shown in the
following diagram:
WARNING: Do not apply any voltage across the input terminal and DC common as this
will cause damage to the TS 7320 controller. Connect only a dry (i.e. voltage-free) contact.