TSC 7320 Transfer Switch Controller
PM180 REV 0 23/02/10 Thomson Power Systems
36
5.6.3. REMOTE OFF LOAD TEST
If a wire connects the controllers input G (PIN 54) to the DC negative terminals, that input
will tell the controller perform an off load test. The controller will run the off load test until
the input is removed. If the wire is removed the controller will return to normal operation.
Note: the front panel indicator LED will remain illuminated while the input is activated.
5.6.4. REMOTE ON LOAD TEST
If a wire connects the controllers input H (PIN 55) to the DC negative terminals, that input
will tell the controller perform an on load test. The controller will run the on load test until
the input is removed. If the wire is removed the controller will return to normal operation.
Note: the front panel indicator LED will remain illuminated while the input is activated.