TSC 80e TRANSFER SWITCH CONTROLLER
PM091 Rev 1 09/02/27 Thomson Technology
53
5. TSC 80e TYPICAL CONNECTION DIAGRAM
TRANSFER CONTROLLER
MODEL TSC 80e
A (L1)
B (L2)
C (L3)
A (L1)
B (L2)
C (L3)
A (L1)
UTILITY SUPPLY SENSING
120-600VAC
50/60Hz
3 PHASE
GENERATOR SUPPLY
SENSING
120-600VAC
50/60Hz
3 PHASE
LOAD SENSING
120-600VAC
50/60Hz
3 PHASE
1
2
3
4
5
6
7
CONNECTION DIAGRAM
1
1
1
UTILITY AND GENERATOR SUPPLIES MUST
UTILIZE A SOLIDLY GROUNDED NEUTRAL
SYSTEM. REFER TO INSTRUCTION MANUAL FOR
ALTERNATE CONNECTIONS
REVISED
08-08-01
NOTE:
3 PHASE, 4 WIRE ATS CONNECTIONS
SHOWN ONLY.
SEE MANUAL FOR ALTERNATE CONNECTION DIAGRAMS
FULL FILENAME
B (L2)
8
C (L3)
9
N
10
COMMON SYSTEM
NEUTRAL OR GROUND
REFERENCE
19
20
25
L
LOAD ON UTILITY SUPPLY INPUT (120VAC)
TRANSFER TO UTILITY OUTPUT
RATED 10A, 120VAC RES. MAX.
2
26
N
UTILITY CONTROL POWER
120VAC
13
12
11
PROG #5
LOAD ON
UTILTY
(DEFAULT)
RATED 10A, 120/250VAC, 5A, 30VDC
RES. MAX.
16
15
14
PROG #4
LOAD ON
GENERATOR
(DEFAULT)
RATED 10A, 120/250VAC, 5A, 30VDC
RES. MAX.
31
30
29
PROG #1
ATS NOT IN AUTO
(DEFAULT)
RATED 10A, 120/250VAC, 5A, 30VDC
RES. MAX.
37
36
35
PROG #2
LOAD DISCONNECT
CONTACT
(DEFAULT)
RATED 10A, 120/250VAC, 5A, 30VDC
RES. MAX.
34
33
32
PROG #3
FAIL TO TRANSFER
(DEFAULT)
RATED 10A, 120/250VAC, 5A, 30VDC
RES. MAX.
28
27
ENGINE START CONTACT
(Contact closes to start
engine on power failure)
RATED 10A, 120/250VAC, 5A, 30VDC RES.
MAX.
JP3
Ribbon Cable To Door
Mounted Lexan Faceplate
22
18
21
L
TRANSFER TO GENERATOR OUTPUT
RATED 10A, 120VAC, 10A RES. MAX.
2
23
N
GENERATOR CONTROL
POWER
120VAC
K4
XFER TO
GEN
K8
17
Utility Interlock
NO CONNECTION
SYSTEM GROUND
24
K8
XFER TO
UTIL
LOAD ON GENERATOR SUPPLY INPUT (120VAC)
2
LOAD SENSING MUST BE CONNECTED FOR
CORRECT OPERATION
2
42
44
38
REMOTE LOAD TEST
(close to activate)
SERVICE ENTRANCE MODE
(close to disable transfer fail logic)
5Vdc Digital Inputs
COM
41
OFF LOAD TEST
(close to activate)
40
ON LOAD TEST
(close to activate)
39
OFF MODE
(close to activate)