EasyManua.ls Logo

Thytronic DMC3S - Residual Overvoltage - 59 N; Residual Emergency Overcurrent - 59 N(Eme)

Thytronic DMC3S
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
DMC3S - Manual - 08 - 2021
Residual overvoltage - 59N
Common configurations:
Type of residual voltage measurement for 59N- direct/calculated (
3
Vo
Type59N
) U
E
/U
EC
Threshold
U
E
>
Type of characteristic (
U
E
>Curve) DEFINITE/INVERSE
[1]
Reset delay (t
UE>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First definite time threshold (
U
E
>
def
) 0.001...1.000 U
En
(step 0.001 U
En
)
Operating time (t
UE
>
def
) 0.05...1000 s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Inverse time
First 59N inverse time threshold (
U
E
>
inv
) 0.001...1.000 U
En
(step 0.001 U
En
)
Operating time
v
(t
UE
>
inv
) 0.10...100.0 s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Threshold
U
E
>>
Reset delay (t
UE>>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Second definite time threshold (
U
E
>>
def
) 0.01...0.70 U
En
(step 0.01 U
En
)
Operating time (t
UE
>>
def
) 0.05...1000 s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Residual emergency overcurrent - 59N(eme)
Common configurations:
Type of residual voltage measurement for 59N- direct/calculated (
3
Vo
Type59N
) U
E
/U
EC
Threshold
U
Eeme
>
Type of characteristic (
U
Eeme
>Curve) INVERSE/DEFINITE
[2]
Reset delay t
UEeme>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First definite time threshold (
U
Eeme
>
def
) 0.001...1.000 U
En
(step 0.001 U
En
)
Operating time (t
UEeme
>
def
) 0.05...1000 s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Inverse time
First inverse time threshold (
U
Eeme
>
inv
) 0.001...1.000 U
En
(step 0.001 U
En
)
Operating time (t
UEeme
>
inv
) 0.10...100.0 s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Note 1 The general formula for inverse time curves is: t= (0.5 ∙ t
UE
>
inv
) / [(U
E
/U
E
>
inv
) - 1]
t = operating time (in seconds)
t
UE
>
inv
= operating time regulation (in seconds)
U
E
= residual voltage (measured directly or calculated according to the measurement type configuration)
U
E
>
inv
= trip threshold regulation
Note 2 The general formula for inverse time curves is: t= (0.5 ∙ t
UEeme
>
inv
) / [(U
E
/U
Eeme
>
inv
) - 1]
t = operating time (in seconds)
t
UE
>
inv
= operating time regulation (in seconds)
U
E
= residual voltage (measured directly or calculated according to the measurement type configuration)
U
E
>
inv
= trip threshold regulation

Table of Contents

Related product manuals