6F8C0845
79
4.3 Requests to the DN611
4
(4) Slave device parameters
PARA_SLAVE structure
DEVICE_ARRAY [0...9] Structural data type   Slave device parameter set value
DEVICE structure
PORT WORD type Port  No.
SLAVE_ADR WORD type Slave node address
VENDOR_ID WORD type Vendor ID
P_TYPE D type Product type
P_CODE WORD type Product code
SCANTYPE WORD type Scan type
POL_BK WORD type Poll background
BS_RCVSIZE WORD type Bit strobe receive size
POL_RCVSIZE WORD type Polling receive size
RESERVED1 WORD type Reserved
POL_SNDSIZE WORD type Polling send size
RESERVED2 WORD type Reserved
MAJOR_REV WORD type Major revision
MINOR_REV WORD type Minor revision
RESERVED3 WORD type Reserved
RESERVED4 WORD type Reserved
For those items marked (*), refer to the manual for the slave devices.
Table 4-14  Slave Device Parameters
Parameter Description
Port No.  Set 0 fixed.
Slave node address Specify a node address for a slave whose parameters are to be set.  
Range of setting: 0 to 63
Vendor ID Specify a vendor ID for a slave whose parameters are to be set. 
(*)Product type    Specify the product type of a slave whose parameters 
are to be set. (*)
Product code Specify the product code of a slave whose parameters are to be set. (*)
Scan type Specify a mode of transmission between DN611 and slave.  (*)   
0:  Bit strobe Other than 0, 1, 2:
1:  Polling Cannot be set.
2:  Bit strobe and polling
Poll background Specify an interval at which DN611 accesses devices.
00:  Scan polling (Access every scan)
01:  Background polling (Access every scans specified in poll ratio)
Bit strobe receive size Specify a size of data from a slave of bit strobe type to DN611 in bytes. (*)
Polling receive size Specify a size of data from a slave of polling type to DN611 in bytes.  (*)
Polling send size Specify a size of data from DN611 to a slave of polling type in bytes.  (*)
Major revision Specify a slave major revision.  (*)
Minor revision Specify a slave minor revision.  (*)
Reserved Set 0.