Chapter 7  Troubleshooting
This chapter describes how to check the causes of trouble and what remedial steps 
should be taken if the DN611 goes wrong during its operation.  Also refer to the 
Sequence Controller User's Manual in dealing with trouble.
7.1  At Module Start
(1) The module does not start normally (is not set in standby mode):
If the module is normal, the DN611 starts initializing the module when power is turned 
on or when reset is requested, and then is set in standby mode.
Standby: MS, NS:  OFF   7-Segment LED: Node address is shown lit.
Figure 7-1 Module Start Check Items
(2) Set in down mode during communication with slave devices
Countermeasure
Replace the module.   Record the down information before replacing the module (as noted on 
the module front).  Send the module which has run down and the down information to TOSHIBA.
START
Is S controller's power 
supplied?
Is the DN611 mounted properly 
in the base unit?
Yes
Yes
Isn't station status down mode?
Yes
Does thee module start properly if it 
is combined with other S controller?
Yes
Replace the S controller.
END
No
No
No
No
Supply the primary power of the S 
controller power module at the rated 
voltage.
Insert it into the slot correctly and tighten 
the setscrew.
Replace the module.  
Read down information, and send it 
together with the module to TOSHIBA.