The completion statuses that DN611 returns in response to the requests issued by the S 
controller are shown below.
Except for normal completion, an error code and the local node address are alternately 
indicated by the 7-segment LED on the front panel of the DN611.  
The error code indication stops when the following request is completed normally.
Table 4-18  List of Completion Statuses
Completion status Code Description
Normal completion 0001H Indicates a request is completed normally.
Local station failure 00A0H When a request for inhibited processing is issued in down 
mode
Serial number 
unregistered
00A1H A serial number registered in the DN611 disappeared →  Ask 
for repair because the DN611 needs resetting.
Local station 
parameters not set 
yet
00A2H A request for inhibited processing is issued when local station 
parameters have not been set yet.
Length error 00A3H Data size of a bit strobe output data write request is 8 bytes or 
more.
Station mode error 00A4H A request for inhibited processing is issued during run mode; a 
request for inhibited processing is issued during standby 
mode.
00A5H Reserved
Transmission 
inhibited
00A6H A request related to transmission is issued by the S controller 
in a state where transmission is inhibited.
Format error 00B0H Requested processing code is not supported
00B1H Inhibited status is demanded by control request
00B2H Requested year is invalid at time setting
00B3H Requested month is incorrect at time setting
00B4H Request day is incorrect at time setting
00B5H Request hour is incorrect at time setting
00B6H Request minute is incorrect at time setting
00B7H Request second is incorrect at time setting
00B8H Incorrect node address (other than 0 to 63) is set in response 
to parameter setting request and explicit message request.
Component data 
error
00C0H Incorrect data is in the data constituting parameter setting 
request. (See trace information for details.)
00C1H Slave device input/output data cannot be allocated to the input/
output data area (when control request RUN is issued).
Memory pool 
acquisition error
00C2H The OS in the DN611 has failed to secure memory.  Switch 
power off and back on to reset the module.