90 ACE-tronics G9 ASD Installation and Operation Manual
Low-Speed Signal Output Frequency
Program Terminal Reach
The Low-Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal for the duration that the
ASD output is equal to or above this setting (see Table 10 on pg. 242 for the
available output assignments).
Direct Access Number — F100
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — M
ax. Freq. (F011)
Units — Hz
Speed Reach Frequency
Program Terminal Reach
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter F102, activates the assigned
output terminal for the duration that the ASD output is within the bandwidth
specified (see Table 10 on pg. 242 for the available output assignments).
This setting is also a permissive when using the Expr
ess Speed function.
Direct Access Number — F101
Parameter Type — N
umerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — M
ax. Freq. (F011)
Units — Hz
Speed Reach Detection Band
Program Terminal Reach
This parameter sets the bandwidth of the Speed Reach Frequency (F101)
setting.
Direct Access Number — F102
Parameter Type — Numerical
Factory Default — 2.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — M
ax. Freq. (F011)
Units — Hz
Input Terminal Priority
Program Terminal Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the ACE G9-120V-PCB even
though the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the ACE G9-120V-PCB will receive priority over
commands from the EOI.
See F260 for additional information on using the Jog function.
See F250 – F252 for additional information on DC Injection Braking.
Settings:
Disabled
Enabled
Direct Access Number — F106
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
w Spe
a
quen
F100 F106
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com