92 ACE-tronics G9 ASD Installation and Operation Manual
Always ON Terminal Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the virtual discrete input
terminal ON. As a virtual terminal, the ON control terminal exists only in
memory and is considered to always be in its True (activated) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to any one of the user-
selectable functions listed in Table 7 on pg. 236.
This terminal is set to ST
(Standby) to allow for ready-to-run operation and
allows for the use of the discrete input terminals for other functions.
Direct Access Number — F110
Parameter Type — Selection List
Factory Default ST
Changeable During Run — No
Input Terminal 1 (F) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the F discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable F terminal to any one of
the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F111
Parameter Type — Selection List
Factory Default Forward
Changeable During Run — No
Input Terminal 2 (R) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the R discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable R terminal to any one of
the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F112
Parameter Type — Selection List
Factory Default Reverse
Changeable During Run — No
Input Terminal 3 (I1) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the I1 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable I1 terminal to any one of
the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F113
Parameter Type — Selection List
Factory Default Preset Speed 1
Changeable During Run — No
Input Terminal 4 (I2) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the I2 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable I2 terminal to any one of
the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F114
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
F110 F114