214 ACE-tronics G9 ASD Installation and Operation Manual
Input Function Target 3
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 3
terminal.
This setting assigns the function of the programmable Input Function Target 3
terminal to any one of the user-selectable functions listed in Table 9 on pg. 241,
Table 10 on pg. 242, or Table 12 on pg. 245.
See F977 for additional information on this parameter.
Direct Access Number — F916
Parameter Type — Selection List
Factory Default 0 (Disabled)
Changeable During Run — Yes
Output Function Assigned
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the Output Function Assigned terminal.
This setting assigns the function of the programmable Output Function
Assigned data location to one of the functions listed in the Input Setting field
of Table 10 on pg. 242.
Settings:
0 – 3099
See F977 for additional information on this parameter.
Direct Access Number — F917
Parameter Type — Selection List
Factory Default 0 (Disabled)
Changeable During Run — Yes
My Function Percent Data 1
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 1.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Once the assigned output value reaches the threshold setting of this parameter
the output value is transferred to My Function Out 1.
See F977 for additional information on this parameter.
Direct Access Number — F918
Parameter Type — N
umerical
Factory Default — 0.00
Changeable During Run — Ye
s
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Percent Data 2
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 2.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number — F919
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye
s
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Percent Data 3
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 3.
The analog signal is selected using the Input Setting number from Table 10 on
pg. 242.
Direct Access Number — F920
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye
s
Minimum — 0.00
Maximum — 200.00
Units — %
F916 F920