ACE-tronics G9 ASD Installation and Operation Manual 251
MS Relay Off/Soft Start
Alarm
MOFF Under-voltage condition at
the 3-phase AC input to the
ASD.
Low 3-phase utility voltage.
Over-Current OC ASD output current greater
th
an F601 setting.
Defective IGBT (U, V, or W).
ASD output to the motor is connected
incorrectly.
ASD output phase-to-phase short.
The ASD is starting into a spinning motor.
Motor/machine jammed.
Mechanical brake engaged while the ASD is
starting or while running.
Accel/Decel time is too short.
Voltage Boost setting is too high.
Load fluctuations.
ASD operating at an elevated temperature.
*Over-Heat OH ASD ambient temperature
excessive.
ASD is operating at an elevated temperature.
ASD is too close to heat-generating
equipment.
Cooling fan vent is obstructed (see Mounting
the ASD on pg. 15).
Cooling fan is inoperative.
Internal thermistor is disconnected.
Over-Torque OT Torque requirement in excess
of the setting of F616 or F617
for a time longer than the
setting of F618.
ASD is not correctly matched to the
a
pplication.
F616 or F617 setting is too low.
Obstructed load.
* Reset ignored if active.
LCD Screen
LED
Screen
Description Possible Causes