50 ACE-tronics G9 ASD Installation and Operation Manual
Command Control Selections
The following is a listing with descriptions of the
Command Mode (F003) selections (Program
Fundamental Standard Mode Selection Command
Mode Selection).
Settings:
0 — Terminal Board
Allows for Command control input via the
Terminal Board.
1 — Not Used
Unused.
2 — EOI Keypad
Used for EOI command control.
3 — RS485
Used to transfer commands to the ASD via RS
485 4-Wire.
4 — Communication Option Board
Use this setting if using the optional Com
munication Board for command control.
Frequency Control
Selections
The following is a listing with descriptions of the
Frequency Mode (F004) selections (Program
Fundamental Standard Mode Selection Frequency
Mode 1).
Settings:
1 — V/I
Used when a 0 to 10 VDC analog input or a 0 – 20 mA DC current input is used as the frequency
c
ontrol input. Only one input signal type may be used at a time. Set SW2 to the desired signal
type.
2 — RR
Used for a 0 to 10 VDC analog input signal.
3 — RX
Used for a ±10 VDC analog input signal.
4 — Not Used
Unused.
5 — EOI Keypad
Used for EOI frequency control.
6 — RS485
Used to transfer speed commands to the ASD via RS
485 4-Wire.
Standard Mode Selection
(F003) Command Mode
Selection
Terminal Block
01:06
(Default)
Standard Mode Selection
(F004) Frequency Mode 1
RR
02:06
(Default)
(Default)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com