ACE-tronics G9 ASD Installation and Operation Manual 87
Preset Speed 1
Program Frequency Preset Speeds
Up to fifteen (15) output frequency values that fall within the Lower-Limit and
the Upper-Limit range may be programmed into the ASD and output as a
Preset Speed. This parameter assigns an output frequency to binary number
0001 and is identified as Preset Speed 1. The binary number is applied to
I1 – I4 of
the ACE G9-120V-PCB to output the Preset Speed.
Perform the following setup to allow the system to receive Preset Speed
control input at the I1 – I4 terminals:
1. Program Fundamental Standard Mode Selection Command Mode
Selection Terminal Board.
2. Program Terminal Input Terminals I1 (set to Preset Speed 1; LSB
of 4-bit count). Repeat for I2I4 (MSB of 4-bit count) as Preset Speed 2
4, respectively (all Normally Open).
3. Program Frequency Preset Speeds Preset Speed 1 (set an output
frequency as Preset Speed 1; repeat for Preset Speeds 2 15 as required).
4. Program Pattern Run Operation Mode Preset Speed Operation
Mode Enabled/Disabled.
Select Enable to use the direction, accel/decel, and torque settings of the
Preset Speed being run. The torque settings used will be as defined in F170
F181 and as selected via the associated discrete input terminals V/
f
Switching 1 and 2 in Table 7 on pg. 236.
Select Disabled to use the speed setting only of the Preset Speed being run.
5. Place the system in the Remote mode (Local/Remote LED Off).
6. Provide a Run command (activate F and/or R).
Activate I1 to run Preset Speed 1 (120 VAC to I1 = 0001 binary).
With I1 – I4 configured to output Preset Speeds (F115F118), 0001 – 1111
may be applied to I1 – I4 of the ACE G9-120V-PCB to run the associated
Preset Speed. If bidirectional operation is required F
and R must be activated.
With I1 being the least significant bit of a binary count, the I1 – I4 settings will
produce the programmed speed settings as indicated in the Preset Speed Truth
Table to the right.
Preset Speeds are also used in the Pattern Run mode.
Direct Access Number — F018
Parameter Type — N
umerical
Factory Default 60.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed Truth Table
Preset Speed 2
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as Preset Speed 2. The binary number is applied to I1I4 of the
ACE G9-120V-PCB to output the Preset Speed (see F018 for additional
information on this parameter).
Direct Access Number — F019
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Pre
set Speed
1
Preset
I4
MSB
I3 I2
I1
LSB
Output
10001 F018
2001 0 F019
30011F020
401 00F021
501 0 1 F022
60110 F023
70111 F024
8 1 000 F287
9 1 001 F288
10 1 0 1 0 F289
11 1 0 11F290
12 1100F291
13 110 1 F292
14 1110 F293
15 1111F294
Note: 1 = Terminal activated.
Pre
set Speed
2
F018 F019