EasyManua.ls Logo

Toshiba P9 - Page 33

Toshiba P9
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P9 ASD Installation and Operation Manual 23
V/I The V/I terminal has the dual function of being able to receive an input voltage or current. The
function as a voltage input is to receive a 0 – 10 VDC input signal. The function as a current input is to
receive a 0 – 20 mA input signal. Using either input type, the function is to control the 0.0 – Maximum
Frequency output or the 0.0 to 250% torque output of the ASD. This is an isolated input terminal. This
terminal may be programmed to control the speed or torque of the motor and cannot process both input
types simultaneously. SW301 must be set to V or I to receive a voltage or current, respectively (see
Figure 9 on pg 24). Terminal scaling is accomplished via F201F206. The gain and bias of this
terminal may be adjusted for application-specific suitability (see F470 and F471).
+SUControl Power Supply Backup input terminal. This terminal accepts the user-supplied
24 VDC backup power to the control circuits (only). Backup power is used in the event of an open
MCCB or during a momentary loss of the 3-phase input power and cannot be supplied by the 3-phase
input power. Parameter settings, real-time clock information, and trip history information are retained
with the use of the +SU backup power.
The P9 ASD is equipped with an EOI-mounted battery for this function. The battery backup has the
added feature of allowing for the transfer of the EOI to another ASD while retaining the control
programming. See the section titled Battery Backup on pg. 28 for additional information on the battery
backup features.
P24 — +24 VDC at 200 mA power supply for customer use.
PP — The function of output PP is to provide a 10 VDC/10 mADC (max.) output that may be divided
using a potentiometer. The tapped voltage is applied to the RR input to provide manual control of the
RR programmed function.
O1A/B (OUT1A/B) — The default function assigned to this terminal is External Device 1. The
function as External Device 1 is to activate/deactivate an auxiliary motor once the Virtual Linear
Pump level has remained above the Maximum threshold setting or below the Minimum threshold
setting for the time setting of F480. The OUT1 terminal is rated at 2 A/120 VAC and 2 A/30 VDC. This
terminal may be set to any of the functions listed in Table 9 on pg. 251 (see F130).
O2A/B (OUT2A/B) — The default function assigned to this terminal is External Device 2. The
function as External Device 2, in conjunction with External Device 1, is to activate/deactivate an
auxiliary motor once the control level of the Virtual Linear Pump settings has remained above the
Maximum threshold or below the Minimum threshold settings for the time setting of F480. The OUT2
terminal is rated at 2 A/120 VAC and 2 A/30 VDC. This terminal may be set to any of the functions
listed in Table 9 on pg. 251 (see F131).
FP — The default function of this output terminal is to output a series of pulses at a rate that is a
function of the ASD output frequency (50 mA max. at 1.0 kHz to 43.3 kHz). As the output frequency of
the ASD goes up, so does the FP output pulse rate. This terminal may be programmed to provide an
output pulse rate that is proportional to the magnitude of the user-selected item from Table 7 on pg. 249.
For additional information on this terminal, see F676 on pg. 206.
AMThis output terminal produces an output voltage that is proportional to the output frequency of
the ASD or of the magnitude of the function assigned to this terminal. The available assignments for
this output terminal are listed in Table 7 on pg. 249. For additional information on this terminal, see
F670 on pg. 204.
FM — This output terminal produces an output current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the function assigned to this terminal. The available
assignments for this output terminal are listed in Table 7 on pg. 249. For additional information on this
terminal, see F005 on pg. 79. The Voltage/Current output selection is performed at F681.
FLA — One of two normally open contacts that, under user-defined conditions, connect to FLC.
SU
4
P
xternal Device
1
A/B
2A/B
LA
L
B

Table of Contents

Related product manuals