Chapter 1    Introducing the PA912 Module 
6F8C1259 
 
1.1.3  Transmission operation upon error 
When the controller is failed to operate properly or an error is detected on the 
TC-net I/O loop, one of the following three output modes can be specified as 
the  output  operation  for  the  PROFIBUS  slave  I/O  devices.  The  transmission 
operation  upon  error  can  be  specified  via  the  nV-Tool  by  using  a  module 
parameter "Transmission operation at emg." of the PA912-M/PA912-NM module. 
The setting method is described in "Chapter 3: Setting." 
Table 1-2    Transmission operation upon error 
Mode  Transmission operation 
Stop  Halts the transmission operation. 
Trans 1  Continues the transmission operation by setting the 
transmission data to the value immediately before the error 
occurrence. 
Trans 2 
(Clear mode) 
PA912 force the Slave module to change the Clear mode 
with the command without data(0 length data and 0 data) . 
As Clear mode, How the Slave module behave is depend on 
the Slave venders specification.   
 
 
Figure 1-5    Setting screen of transmission operation upon error 
 
CAUTION
Pay due consideration to the system operation 
b
efore specifying the operation mode of the PA912 
upon error. 
 
Mandatory