EasyManua.ls Logo

Toshiba PA912 - Switch Setting; TC-Net I;O Loop Address Setting Switch (STN-H, STN-L); Setting

Toshiba PA912
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 3 Setting
6F8C1259
28
3.1 Switch Setting
The switches that determine the operation mode and TC-net I/O loop address
of PA912 are on the BU90A unit.
The method to set the switches is shown below.
Important
Set the switches that determine the operation mode and station address of the PA912 module
before turning the power on.
3.1.1 TC-net I/O loop address setting switch (STN-H, STN-L)
TC-net loop address setting switches are hexadecimal rotary switches that
determine the loop address on the TC-net I/O loop.
Set the station address (3 to 34) that has been assigned upon system
configuration in a HEX code (03 to 22 (h)). Assign an address with a different
value to each of the nodes in the system.
Table 3-1 shows the setting of a TC-net I/O loop address.
Figure 3-1 TC-net I/O loop switch setting configuration
Table 3-1 TC-net I/O loop address setting
Name Description Remark
Setting range : 03 to 22(h)
STN-H(upper digit address): 0 to F(h)
STN-L(lower digit address): 0 to F(h)
00h is set as a
factory default
STN-H
STN-L
(Note) (h) indicates hexadecimal.
Set the station address in hexadecimal.
For example, if the address value is 28, it is ‘1C (h) when converted to
hexadecimal. Therefore, set as follows:
STN-H side: ‘1’
STN-L side: ‘C’
For decimal-hexadecimal conversion, refer to "Appendix D
Decimal-hexadecimal conversion table."

Table of Contents

Related product manuals