3.2 Setting the Slave Device Configuration Information
Unified Controller nv series PROFIBUS(PA912) Module Instruction Manual
35
3
Select the GSD file, and click the [Open] button.
Figure 3-7 Selecting the GSD file
Note
If version 4.6.0 or later of the nV-Tool is installed, Toshiba GSD file (TSB_0C32_V2.gsd) for
the PA912 is also installed in the same folder of the nV-Tool.
Important
The PA912 is restricted to use the combination of the versions between PA912 firmware
and the GSD.( See the combination versions described in "Chapter 1.1: Functions and
Characteristics of the PA912 Module".) If the correct combination of versions is not used,
the input and output data is set to be incorrect.
To avoid to use the incorrect combination of the versions PA912 firmware and Gsd.
Confirm the versions of the PA912 firmware version with nV-Tool.
To enable byte-swapp mode,PA912 firmware version V2.20 or later and nV-tool version also
4.8.3 or later