Chapter 3 Setting
6F8C1259
6
Set properties of the slave I/O device.
Set the input and output addresses in the Module properties screen.
Figure 3-14 Slave I/O property setting
◆
◆◆
◆
Important
・
The minimum data type of the I/O variable in the nV-Tool can be set in increments of 1 word.
The Start Address of the slave I/O device must start with an even byte address.
If an odd byte address is specified, the configuration cannot be imported to the nV-Tool.
・
The Start Address of the slave I/O device must start with a multiple-of-4 byte address in the
case of using 2W length data (DINT, REAL, DWORD, TIME, TOD, DATE) in the nV-Tool.