6F3B0253
128 T1-16S User’s Manual
7. Instructions
( N )
Negative pulse coil
Expression
A
Input (
N
)
Function
When the input is changed form ON to OFF, the device A is set to ON for 1 scan time.
This instruction is used to detect the input changing from ON to OFF.
Execution condition
Input Operation Output
OFF When the input at last scan is OFF, sets A to OFF
When the input at last scan is ON, sets A to ON
ON Sets device A to OFF
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
A Device
√√√
Example
R101 comes ON for only 1 scan when X000 is changed from ON to OFF.
X000
R100
1 scan time 1 scan time
Note
The maximum usable number in a program is 2048.
(
PN(P)(N)
total)