EasyManua.ls Logo

Toshiba PROSEC T1-16S - I;O Modules

Toshiba PROSEC T1-16S
301 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F3B0253
Basic Hardware and Function
25
1. System Configuration
1.5.2 I/O modules
The T1-16S can connect up to eight I/O modules.
The following 10 types of the I/O modules are available.
For specification details of the I/O modules, refer to the separate manual “T1-16S
User’s Manual I/O Modules “.
Type
Description
Power supply
DI116M
16 points input, 24Vdc – 5mA
DO116M
16 points output, 24Vdc – 100mA
DD116M
8 points input, 24Vdc - 5mA
+ 8 points output, 24Vdc – 100mA
RO108M
8 points relay output, 24Vdc/240Vac - 1A
AD121M
1 channel analog input, 0 to 5V / 0 to 20mA
AD131M
1 channel analog input, ±10V
DA121M
1 channel analog output, 0 to 20mA
DA131M
1 channel analog output, ±10V
TC111M
1 channel thermo-couple input
FR112M
TOSLINE-F10 remote station,
1 word input + 1 word output
Supplied from the
basic unit (5 Vdc)
Expantion connector Expantion connectors
FR112M
Other I/O modules
(1) If more than 8 I/O modules are connected, T1-16S cannot operate normally.
(2) The TOSLINE-F10 remote station module (FR112M) must be connected at the
right end. Tow or more FR112Ms cannot be used together.
NOTE