T1-16S User’s Manual
1. System Configuration
1.8 Real-time data link system
TOSLINE-F10
TOSLINE-F10 is a high speed data transmission system suited for small points I/O
distribution system. By inserting the TOSLINE-F10 remote module (FR112M), the
T1-16S can work as a remote station of the TOSLINE-F10 network. On this network,
the T1-16S sends 1 word data to the master station and receives 1 word data from
the master station.
Item
TOSLINE-F10 system specifications
High speed mode
Long distance mode
Topology
Bus (terminated at both ends)
Transmission distance
(without repeater)
500 m max. (total)
1 km max. (total)
Transmission speed
750 kbps
250 kbps
Scan transmission
capacity
512 points (32 words) max.
Scan cycle
7 ms/32 words
12 ms/32 words
Error checking
CRC check
Typical data link configuration
The figure below shows the typical data link configuration.
NOTE
T2E
(master)
T2E
(remote)
Master
computer
RI/O RI/O T1-16S
TOSLINE-F10
RI/O: remote I/O
Operator interface units
T1-16S T1-16S
(1) Refer to the separate “T1 User’s Manual Option Card and I/O
Module “ for details of the TOSLINE-F10 remote card (FR112).
(2) Refer to the separate TOSLINE-F10 User’s Manual for details of
overall TOSLINE-F10 system.