27
1. System Configuration
1.6 Programmer port function
The interface of the T1-16S’s programmer port is RS-232C. Normally this port is
used to connect the programmer. However, this port can also be used for the
computer link function.
The computer link is a data communication function between computer or operator
interface unit and the T1-16S. The data in the T1-16S can be read and written by
creating simple communication program on the computer. The computer link protocol
of the T1-16S is published in “T1-16S User’s Manual Communication Function ”.
Item
Specifications
Interface
Conforms to RS-232C
Transmission system
Half-duplex
Synchronization
Start-stop system (asynchronous)
Transmission speed
9600 bps (fixed)
Transmission distance
15 m max.
Framing
Start bit:
Data bits:
Parity:
Stop bit:
1 bit
8 bits (fixed)
Odd or none
1 bit (fixed)
Protocol
T-series computer link (ASCII)
Programmer (binary)
Transmission delay option
0 to 300 ms
By using the multi-drop adapter (CU111), multiple T1-16Ss can be connected on an
RS-485 line. The T-series PLC programming software (T-PDS) can also be used in
this configuration.
T1-16S
C
U
Operator Interface
Master Computer
RS-232C
RS-485 (1 km max.)
Max. 32 T1-16Ss
T1-16S
C
U
T1-16S
C
U
T1-16S

Table of Contents