T1-16S User’s Manual
1. System Configuration
Analog setting adjusters:
Two analog setting adjusters are provided. The V0 value is stored in SW30 and the
V1 value is stored in SW31. The converted value range is 0 to 1000. Refer to section
8.5 for details of the analog setting function.
Programmer port connector:
Used to connect the programmer cable. The interface is RS-232C. This port can also
be used for the computer link function. Refer to section 1.6 for more information
about the computer link function.
Expansion connector:
Used to connect the I/O module.
RS-485 port (Enhanced model only):
Used to connect a computer (SCADA system), operator interface unit, other T1-16S,
or many kinds of serial ASCII devices including Toshiba’s Inverter through RS-485
interface. Refer to section 1.7 for more information about the T1-16S’s RS-485 multi-
purpose communication functions.
Mounting holes:
Used to fix the T1-16S on a mounting frame by screws. The mounting holes are
provided at two opposite corners.
Use two M4 screws for mounting. See section 4.2 for
installing the unit.
DIN rail bracket:
The DIN rail bracket is provided at the rear for mounting the T1-16S on a 35 mm DIN
rail. See section 4.2 for installing the unit.