EasyManua.ls Logo

Toshiba PROSEC T1-16S - Page 185

Toshiba PROSEC T1-16S
301 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F3B0253
Basic Hardware and Function 183
7. Instructions
FUN 101
<=
Less than or equal
Expression
Input [ A <= B ] Output
Function
When the input is ON, the data of A and the data of B are compared, and if A is less than or equal
to
B
, the output is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution
A B
ON
A > B
OFF
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
A Compared
data
√√√√√√√√√√
B Reference
data
√√√√√√√√√√
Example
When R00C is ON, the data of D0125 is compared with the constant data -100, and if the data
of D0125 is less than or equal to -100, R020 is turned ON.
If the data of D0125 is -150, the comparison result is true. Consequently, R020 is turned ON.
D0125 -150 < Constant -100 R020 is ON
If the data of D0125 is 0, the comparison result is false. Consequently, R020 is turned OFF.
D0125 0 Constant -100 R020 is OFF
Note
This instruction deals with the data as signed integer (-32768 to 32767).

Table of Contents