EasyManua.ls Logo

Toshiba PROSEC T1-16S - Page 223

Toshiba PROSEC T1-16S
301 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F3B0253
Basic Hardware and Function 221
7. Instructions
PID algorithm:
∆∆
MV K P I D
MV MV MV
nnnn
nn n
P
=⋅ ++
()
1
Here,
Pee
eSVPV
nnn
nnn
=−
=−
1
I
etIr
T
n
n
I
=
⋅+
D
TPV PV tD Dr
tT
DD D
n
nn n
nn n
D
D
=
⋅−+
+⋅
=+
=
−−
()
.
11
1
01
η
η
Parameter details
A Process input value PVC (0.00 to 100.00 %) Data range: 0 to 10000
A+1 Auto mode set value ASV (0.00 to 100.00 %) Data range: 0 to 10000
A+2 Cascade mode set value CSV (0.00 to 100.00 %) Data range: 0 to 10000
A+3 Manual mode MV MMV (-25.00 to 125.00 %) Data range: -2500 to 12500
A+4 MV tracking input TMV (-25.00 to 125.00 %) Data range: -2500 to 12500
A+5 Mode setting MODE
FC840
Operation mode
00 : Manual mode
01 : Auto mode
10 : Cascade mode
11 : (Reserve)
Tracking designation
0 : No
1 : Yes
B Proportional gain K
P
(0.00 to 327.67) Data range: 0 to 32767
B+1 Integral time T
I
(0.000 to 32.767 min., I
n
=0 if T
I
=0) Data range: 0 to 32767
B+2 Derivative time T
D
(0.000 to 32.767 min.) Data range: 0 to 32767
B+3 Gap (dead-band) GP (0.00 to 10.00 %) Data range: 0 to 1000
B+4 Auto mode initial set value ISV (0.00 to 100.00 %) Data range: 0 to 10000
B+5 Input filter constant FT (0.000 to 0.999) Data range: 0 to 999
B+6 ASV differential limit DSV (0.00 to 100.00 %/t) Data range: 0 to 10000
B+7 MMV differential limit DMMV (0.00 to 100.00 %/t) Data range: 0 to 10000
(If GP 0, Gap is applied)
(If T
I
= 0, then I
n
= 0)
(Fixed)

Table of Contents