182 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Communication Time-Out (Modbus)
Program Communications Ethernet Settings
This parameter plays a role in the setup of the communications
network by setting the time that no activity may exist over the
communications link before the link is severed (Time Out).
The communications network includes other ASDs and Host/
Control computers that monitor the status of the ASD(s), trans-
fers commands, and loads or modifies the parameter settings of
the ASD.
Changes made to this parameter require that the power be
cycled (Off then On) for the changes to take effect.
Direct Access Number —
F594
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 60.0
Motor Overload Protection Level 1
Program Fundamental Motor Set 1
This parameter specifies the motor overload current level for
Motor Set 1. This value is entered as either a percentage of the
full load rating of the ASD or as a percentage of the FLA of the
motor.
The unit of measurement for this parameter may be set to A/V
(Amps) or it may be set as a percentage of the ASD rating. The
nameplated FLA of the motor may be entered directly when
Amps is selected as the unit of measurement (use F701 to
change the display unit).
Motor Overload Protection Level 1 settings will be displayed in
Amps if the EOI display units are set to A/V rather than %.
Direct Access Number —
F600
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 100
Units — %
Stall Prevention Level
Program Protection Stall
This parameter specifies the output current level at which the out-
put frequency is reduced in an attempt to prevent a trip. The over-
current level is entered as a percentage of the maximum rating of
the ASD.
Note:
The Motor Overload Protection parameter must be enabled
at F017
to use this feature.
Direct Access Number —
F601
Parameter Type — Numerical
Factory Default — 150
Changeable During Run — Yes
Minimum — 10
Maximum — 165
Units — %
F594 – F602