Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
My Function Frequency Data 3
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Frequency Data 1.
The analog signal is selected using the Input Setting number
from Table 12 on page 257.
Direct Access Number
F925
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — %
My Function Frequency Data 4
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Frequency Data 4.
The analog signal is selected using the Input Setting number
from Table 12 on page 257.
Direct Access Number
F926
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — %
My Function Frequency Data 5
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Frequency Data 5.
The analog signal is selected using the Input Setting number
from Table 12 on page 257.
Direct Access Number
F927
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum Maximum Freq.
(F011)
Units — %
My Function Time Data 1
Program My Function My Function Data
This parameter is used to set the response delay of the My Func-
tion Time Data 1 terminal.
The applied discrete input signal must be present at the input ter-
minal of the Q9 Plus ASD for the time setting here for a system
response.
Discrete terminal input activation that does not equal or exceed
this setting will be ignored.
Direct Access Number
F928
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
F925F929