Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Table 15. My Function Operator Selections.
My Function Computational Selections
Input
Function
Command
Function Name Function Description
0
NOP (No Opera-
tion)
Disables the My Function feature.
1 ST Execute data read/transfer.
2 STN Execute inverted data read/transfer.
3 AND Logical product of A AND B.
4 ANDN Logical product of A AND B
.
5 OR Logical sum of A OR B.
6 ORN Logical sum of A OR B
.
7 EQ Compares data — Outputs 1 if Equal; 0 if not Equal.
8 NE Compares data — Outputs 0 if Equal; 1 if not Equal.
9 GT Compares data — Outputs 1 if A>B; 0 if AB.
10 GE Compares data — Outputs 1 if AB; 0 if AB.
11 LT Compares data — Outputs 1 if AB; 0 if AB.
12 LE Compares data — Outputs 1 if AB; 0 if A>B.
13 ASUB Outputs absolute difference between A and B — |A–B|
14
FB_ON_DELAY
(Timer)
Enables the On response time delay settings of My Function Time
Data 1 – 5 (F928 – F932) for My Function Data.
15
FB_OFF_DELAY
(Timer)
Enables the Off response time delay settings of My Function Time
Data 1 – 5 (F928 – F932) for My Function Data.
16
FB_COUNTER1
(Timer)
Outputs a 1 upon reaching the pulse count setting of F933.
17
FB_COUNTER2
(Timer)
Outputs a 1 upon reaching the pulse count setting of F934.
18 FB_PEEK_HOLD
Outputs the peak output value since powering up or since the last
reset.
19 SET Sets data.
20 RESET Resets data.
21 CLR Clears data.
22 CLRN Retains data.