NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1 Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable height
difference : 12m
Allowable pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 12.7mm
Thickness : 0.8mm
Pulse Modulating
valve at liquid side
TD
4-way valve
Compressor
KSN108D22UFZ
TS
T2
Outdoor heat
exchanger
Temp. measurement
Propeller fan
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
Max. : 20m
Min. : 2m
Chargeless : 15m
TO
Strainer
RAS-B16G3KVSG-E, RAS-B16G3KVSGB-E / RAS-16J2AVSG-E1
Strainer
Refrigerant amount : 0.80kg
NOTE :
The maximum pipe length of this air c
onditioner is 15 m. When the pipe length exceeds 15m, the additional
charging of
refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
- 25 -