Item
Operation flow and applicable data,etc
Description
20. QUIET mode
Quiet mode is the system which, control the
revolving speed of indoor fan to work
constantly at lower than speed L. In addition,
noise level of indoor unit is less than usual.
Remarks :
1.
2.
Quiet mode is unable to work in dry mode.
Quiet mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating
capacity.
The "Quiet mode" selected from [
] button;
-
The fan of the indoor unit will be restricted the revolving
speed at speed UL.
-
The compressor speed is controlled as show in
the figure.
] button is The "Quiet mode" is canceled by [
pressed to select other speed.
Model 07k 10k 13k 16k
Cool min (Hz) 20.4 20.4 20.4 20.4
Quiet Cool (Hz)
30.6 30.6 34.8 45.0
Heat min (Hz) 20.4 20.4 20.4 20.4
Quiet Heat (Hz) 30.6 30.6 55.2 55.2
18. Fireplace
Operation
19. 8C heating /
Frost
protective
operation
Intended for cold latitudes and
performs objective heating operation.
Press TEMP button down on remote controller
in heating mode until set temperature lower
than
17C .
Set temperature is performed for
5C to
16C
and no cold draft prevention control.
Fireplace 1:
Cancel cold draft prevention control and fan
speed depend on user require base on basic
control.
Fireplace 2:
Cold draft prevention control is active with
super low fan speed (640 rpm).
Keep air circulation during other heat
source applied.
Note:
With Fireplace operation on heating
mode indoor unit always runs and cold
air breezing might be occurred.
Fireplace Operation
1. Press MENU button for enter menu setting
and press TEMP. button to select
FIREPLACE.
2. Enter FIREPLACE set by press MENU button.
3. Select FIREPLACE operation by press
TEMP. button.
4. Confirm selected feature by press MENU
button again.
5. Leave from menu setting display by select
EXIT.
FIREPLACE 1 FIREPLACE 2 None