Item
Operation flow and applicable data,etc
Description
17. Silent
Operation
Silent Operation description
Compressor
frequncy
(rps)
CDU
Fan Speed
(rpm)
Compressor
frequncy
(rps)
CDU
Fan Speed
(rpm)
Silent1
34.8 Max 800 53.4 Max 800
Silent2
22.2 520 37.2 520
Silent1
54.0 Max 860 57.0 Max 860
Silent2
28.2 600 38.4 600
Silent1
56.4 Max 900 64.8 Max 900
Silent2
31.8 600 49.2 600
Model
Silent
Operation
Cooling
RAS-10J2AVSG-E1
Heating
RAS-13J2AVSG-E1
RAS-16J2AVSG-E1
Silent1 28.2 Max 800 40.2 Max 800
Silent2
20.4 520 27.0 520
RAS-07J2AVSG-E1
16. POWER
Selection
Mode
1. Purpose
The function is used when its circuit
breaker is shared with other electrical
appliances. It limits the maximum
current/ power consumption to 100%,
75% or 50%.
The lower the percentage, the higher
the saving and also the longer the
compressor lifetime.
2. Description
When the level is selected, Power-SEL
level flashes on LCD display for 3
seconds. In case of 75% and 50%
level, number "75" or "50" also flashes
for 2 seconds.
Note :
Due to the reason that POWER
SELECT FUNCTION limits the
maximum current, inadequate
capacity may occur.
To automatically control room temperature to
save energy (except in DRY and FAN ONLY
mode)
1. Press MENU button for enter menu setting
and press TEMP. button to select
POWER-SEL.
2. Enter POWER-SEL setting by press MENU
button again.
3.
4.
5.
Select POWER-SEL level by press TEMP.
button.
Confirm POWER-SEL level by press MENU
button.
Leave from menu setting display by select
EXIT.
100% 75% 50%
− Power Selection 75% is 75% of maximum
current.
− Power Selection 50% is 50% of rate maximum
current.
POWER-SELECTION AND SILENT OPERATION
POWER-SELECTION AND SILENT OPERATION
SILENT#1 SILENT#2 None
This function is used when the user need
to keep silent at outdoor side. It is limit
maximum compressor speed and CDU
fan speed. Sound level can be
implemented by 2 silent level.
Sound level:
Rated level > Silent 1 > Silent 2
Note:
Due to Silent operation reason,
In adequate cooling/heating capacity may
occur.
1. Press MENU button for enter menu selection.
During triangle mark blink can select menu by
press TEMP. button.
2. Enter SILENT set by press MENU button.
3. Select SILENT operation by press TEMP.
button.
4. Confirm selected feature by press MENU
button again.
5. Leave from menu setting display by select
EXIT.
Silent 1:
Cooling/heating capacity
is limited maximum for
70% of rated. Only compressor speed is limited.
Silent
2:
CDU sound level is limited for lowest
CDU sound
level. Compressor and CDU fan
speed are limited.