– 39 –
SHRM
DN
01
02
03
04
06
0d
0F
10
11
12
13
14
19
1E
28
29
2A
2E
30
31
32
33
40
5d
60
62
92
Item
Filter sign lighting
time
Dirty state of filter
Central control
address
Specific indoor unit
priority
Heating temp shift
Existence of
automatic cool/heat
mode
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Flap type
(Adjustment of air
direction)
Temp difference of
automatic cooling/
heating mode
selection COOL →
HEAT, HEAT →COOL
Automatic restart of
power failure
Operation condition
of humidifier
Selection of option/
error input (CN70)
HA terminal (CN61)
select
Automatic elevating
grille
Ventilating fan
control
TA sensor selection
Temperature unit
select
Control for humidifier
(+ drain pump control)
High ceiling selection
(Air volume selection)
Timer set
(Wired remote
controller)
Smudging-proof
control clear
Outside interlock
release condition
Description
0000 : None 0001 : 150H
0002 : 2500H 0003 : 5000H
0004 : 10000H
0000 : Standard 0001 : High degree of dirt
(Half of standard time)
0001 : No.1 unit to 0064 : No.64 unit
0099 : Unfixed
0000 : No priority 0001 : Priority
0000 : No shift 0001 : +1˚C
0002 : +2˚C to 0010 : +10˚C
(Up to +6 recommended)
0000 : Provided 0001 : Not provided
(Automatic selection from
connected outdoor unit)
0000 : Heat pump 0001 : Cooling only
(No display of [AUTO] [HEAT])
0000 : (1-way air discharge cassette)
0001 : (4-way air discharge cassette) to 0037
0000 : Unfixed 0001 to 0034
0001 : No.1 unit to 0030 : No.30 unit
0001 : No.1 unit to 0064 : No.64 unit
0000 : Individual 0001 : Header unit of group
0002 : Follower unit of group
0000 : Not provided 0001 : Swing only
0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : 0 deg to 0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None 0001 : Reset
0000 : Usual 0001 : Condition ignored
(Detection control for heat exchanger temperature)
0000 : Filter input 0001 : Alarm input (Air washer, etc.)
0002 : Humidifier input
0000 : Usual 0001 : Leaving-ON prevention control
0000 : Unavailable 0001 : Available
(Standard, (Auto grille, Oil guard,
Oil guard panel) Auto grille panel)
0000 : Unavailable 0001 : Available
0000 : Body TA sensor 0001 : Remote controller sensor
0000 : ˚C (at factory shipment) 0001 : ˚F
0000 : None 0001 : Humidifier + Vaporizing system
(Pump ON)
0002 : Humidifier + Ultrasonic system
(Pump ON after specified time passed) (Unused)
0003 : Humidifier + Natural drain system (Pump OFF)
[4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : Standard filter
0001 : Super-long life
[Concealed Duct Standard type]
0000 : Standard static pressure 0001 : High static pressure 1
(40Pa) (70Pa)
0003 : High static pressure 2 0005 : Correspond to quiet sound
(100Pa) 0006 : Low static pressure (20Pa)
0000 : Available (Operable) 0001 : Unavailable (Operation prohibited)
0000 : Clear
0000 : Operation stop 0001 : Release communication signal
receive
At shipment
According to type
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2˚C
(Floor type 0000: 0˚C)
0001 : Not provided
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0000 : Usual
0002 : Humidifier
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Unavailable
0000 : Body TA sensor
0000 : ˚C
0003 : Humidifier ON,
Pump OFF
0000 : Standard
0000 : Available
4- way Air Discharge
Cassette type only
0000 : Operation stop