– 40 –
SHRM-i
DN Item Description At shipment
01
Filter display delay timer According to type0000: None
0002: 2500H
0004: 10000H
0E
FS unit
Connection set of multiple
indoor units
0000:Standard0000: Standard (1 FS unit : 1 indoor unit)
0001: Multiple units connected ((1 FS unit : Multiple indoor units)
0001: 150H
0003: 5000H
06
Heating temp shift 0002: +2 C
(Floor type 0000: 0 C)
0000: No shift
0002: +2 C
0001: +1 C
0010: +10 C
(Up to +6 recommended)
03
Central control address 0099: Unfixedto
to
0001: No.1 unit
0099: Unfixed
0064: No.64 unit
12 Line address 0099: Unfixedto0001: No.1 unit 0030: No.30 unit
1E
Temp difference of
[AUTO] mode selection
COOL HEAT,
HEAT COOL
0003: 3 deg
(Ts ±1.5)
to0000: 0 deg
(For setup temperature, reversal of COOL/HEAT by } (Data value)/2)
0010: 10 deg
13 Indoor unit address 0099: Unfixedto0001: No.1 unit 0048: No.48 unit
31 Ventilating fan control 0000: Unavailable0000: Unavailable 0001: Available
32 TA sensor selection 0000: Body TA sensor0000: Body TA sensor 0001: Remote controller sensor
33 Temperature unit select 0000: C0000: C (at factory shipment) 0001: F
11
Indoor unit capacity According to capacity
type
0000: Unfixed 0001 to 0050
28
Automatic restart of
power failure
0000: None0000: None 0001: Restart
F0
Swing mode 0001: Standard0001: Standard
0003: Cycle swing
0002: Dual swing
F1
Louver fixed position
(Louver No.1)
0000: Not fixed0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
F2
Louver fixed position
(Louver No.2)
0000: Not fixed0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
F3
Louver fixed position
(Louver No.3)
0000: Not fixed0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
F4
Louver fixed position
(Louver No.4)
0000: Not fixed0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
2A
Selection of option/error
input (CN70)
0002: None0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.)
2E
HA terminal (CN61)
select
0000: Usual
(HA terminal)
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control
04
Specific indoor unit
priority
0000: No priority0000: No priority 0001: Priority
14
Group address 0099: Unfixed0000: Individual
0002: Follower unit of group
0001: Header unit of group
19
Group address According to type0000: No louver
0002: (1-way Cassette type, Ceiling type)
0003: (2-way Cassette type)
0004: (4-way Cassette type)
0001: Swing only
02
Dirty state of filter 0000: Standard0000: Standard
0001: High degree of dirt (Half of standard time)
0d
Existence of [AUTO]
mode
0001: Not provided0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0F
Cooling only 0000: Heat pump0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
10
Type Depending on model
type
0001: 4-way Cassette