IF08CZ10 April, 2019 - 17 -
General Control Specifications Continued:
General Control Specifications
Item Standard specification Option Remarks
Analog signal output
10VDC x 2 programmable channels on EXIO brd.
10VDC x 1 Fixed on XIO brd.
10VDC x 5 programmable channels on EXIF brd.
Connected
measuring
equipment must
be isolated from
ground
Analog signal input
10VDC x 3 channels on EXIO brd.
10VDC x 1 channels on XIO brd.
Connected
source
equipment must
be isolated from
ground
Digital input 6 Programmable on EXIO brd.
Photo coupler 50mA 5-24Vdc
7 Fixed on EXIO brd.
Dry contact 30Vdc 250Vac
8 Fixed on EXIF brd.
Photo coupler 50mA 5-24Vdc
4 Programmable on XIO brd.
Photo coupler 50mA 5-24Vdc
2 Fixed(UVS1 & UVS2) on XIO brd.
Photo coupler 50mA 5-24Vdc
Fixed contact is
always used for
interlocking
control function
Digital output 11 Programmable on EXIO brd.
6 dry contact 30Vdc 250Vac
5 photo coupler 50mA 5-24Vdc
2 Fixed on EXIO brd.
Dry contact 30Vdc 250Vac
6 Fixed on XIO brd.
4 photo coupler 50mA 5-24Vdc
2 dry contact 30Vdc 250Vac
4 Programmable on XIO brd.
Photo coupler 50mA 5-24Vdc
24V contact
always used for
internal control
functions
Commissioning and
Maintenance Tool
Parameter setting,
fault data display,
etc.
Optional
Software
Package